IFPA-120-1P-35A Features
Shift Controls full featured integrated temperature control panels feature industry leading control, integration, and safety. All panels are manufactured in the United States with the highest quality components and construction standards.
ELECTRICAL SPECIFICATIONS
|
|
Voltage | 120 VAC |
Frequency | 60 Hz |
Phases | Single |
Full Load Current Rating | 35 Amps |
Power Rating | 4.20 kW |
Power Controller | SCR (Zero-Cross) |
Short Circuit Current Rating (SCCR) | 100kA |
CONTROLLER FEATURES AND CONTROL SYSTEM INTEGRATION
|
|
Digital Temperature Controller | Advanced PID Controller with Autotuning, Temperature Ramping and Programmable Profiles, 10-Segment LED Power Output Display, Color Changing Display Face when in Alarm, Temperature Filtering |
Front Panel Mounted SAFE/RUN Switch | When the control switch is in the SAFE position, Controller is set to Stop mode and the Safety Contactor is Opened |
MODBUS Interface | Addressable RS-485 MODBUS Communication (RTU or ASCII) Data Register Tables and Communication Protocols are Detailed in the Manual |
Analog Temperature Retransmit | 4-20 mA Sourcing Signal Available Through Terminal Blocks |
Programmable Over-Temperature Alarm/Status | 250VAC, 5 Amp, Dry-Contact, Normally Open Relay Contact Available Through Terminal Blocks |
Optional Remote Enable | 24 VDC or 120 VAC Interlock Relay Available |
SAFETY
|
|
Electrical Construction | All Internal Terminals and Components are Finger-Safe (IP20) Electrical Design and Construction Excced NEC and UL-508A Standards |
Main Power Fusing | Class J Fast Acting Fuses Included Disconnecting Fuse Holder |
Control Power Fusing | 1 Amp 5x20mm Glass Fast Acting Fuse Included Disconnecting and Indicating Fuse Holder |
Heater Load Disconnect- Safety Contactor Opens Upon |
Overtemperature Condition - Programmable and Latching Front Panel Safe/Run Switch Placed in Safe Position Open Thermocouple or Open Sensor Optional External Interlock |
Factory Acceptance Testing | Fully Inspected and Tested Under Load Before Shipment |
Agency Approvals | All Components are UL Listed or Recognized |
CONSTRUCTION
|
|
Components | Securely Mounted with Grounded DIN Rail Mounts Name Brand American and German Manufacturers |
Wiring Connections | Labeled Terminal Blocks Used for Wiring Connections Wires Terminated with Ferrules or Spade Ends, Clearly Labeled with Wire Numbers Corresponding to Included Wiring Diagrams |
Enclosure | 16" x 14" x 7.8" (H x W x D) |
ENVIRONMENTAL SPECIFICATIONS
|
|
Enclosure Material | Polycarbonate Enclosure with Stainless Steel Hardware |
Environmental Rating | NEMA 4X Washdown Rated, IP66 |
Ambient Temperature Rating | 32 to 95°F (0 to 35°C) Indoor Use Only |
Storage Temperature Range | -4°F to 149°F (-20°C to 65°C) |
Relative Humidity | 10-85% Non-Condensing |
Altitude | 2000m or less |
PRODUCT OPTIONS
|
|
Remote/External Enable | 24VDC or 120 VAC Coil Interlock Relay Energize to set Controller in RUN Mode and Close Safety Contactor De-Energize to set Controller in SAFE Mode and Open Safety Contactor |